2008/02-tjc-New Orleans Adolescent Hospital (NOAH)__!1Ad1Ca


29 Feb 2008



Name    Ilana Reisin

E-mail   
ireisin@dhh.la.gov

Facility Name    New Orleans Adolescent Hospital (NOAH)__!1Ad1Ca

Facility CEO    Richard Kramer

Facility Address    210 State Street

New Orleans, LA 70115

Facility Description (Brief)    Facility Description (Brief)

# Beds - Adult    30

# Beds - Child & Adol    15

# Beds - Sub Abuse 

# Beds - Forensic   

# Beds - MR/DD  


# Beds - TotaL    45

# Beds - CMS Distinct Part    30




Survey Type    Unannounced

Surveying Agency    JCAHO


Survey Dates (inclusive)    2/26-29/08

Survey Days (e.g., Mon - Weds)    Tues-Fri

Number of Surveyors    2

Priority Focus Areas    Can't recall




Last Survey Ending Date    4/25-27/05




Profile - Surveyor #1    Edith A. Barrett, RN   [EAB]

•Team Leader

•Trained in TJC BHC Manual

•Experienced surveyor, fair




Profile - Surveyor #2    Neil J. Bryant, MS   [NJB]

•Life Safety Code Specialist



# of Non-Compliant Standards    3




APR/NPSG Cites (Tag#/EP#/Brief Descrip/Surveyor)   


*NPSG 15A EP#1  [EAB]

--Record did not ID specific factors that may increase or decrease risk of suicide




RI/PC/MM/IC Cites (Stnd#/EP#/Brief Descrip/Surveyor)   



  • •PC.5.20 EP#3 - 2 of 3 students did not have immunizations records  [EAB]




  • *PC.16.50 EP#4   [EAB]


--Glucometers used for pt testing have onlyone level of testing




PI/LD/HR/IM Cites (Stnd#/EP#/Brief Descrip/Surveyor)   




EC Cites (Stnd#/EP#/Brief Descrip/Surveyor)   



  • EC.5.20 EP#1  [NJB]



--Fire wall with non-rated door/frame

--fire doors did not have latching hardware

--door coordinator prevented closing and latching

--non-rated foramused to seal penetration

--storage room not protected with automatic fire sprinkler



  • EC.5.40 EP#1,3,8,12,13,15  [NJB]


--Fire alarm inspection reports did not include supervisory devices

--Quarterly inspections of automatic sprinkler system not completed

--Fire extinguisher inspection late

--5-year Standpipe system testing not completed




  • *EC.1.10 EP#9  [EAB]



--R&S rooms have blind spots in the corners




MS/NR Cites (Stnd#/EP#/Brief Descrip/Surveyor) 




**Surveyor Compliments (Policies, Procedures, etc noted by which surveyor)  



**Misc Comments, Suggestions, Etc  

Ilana Reisin


***HM*** RTP***DIS***MBR*** CAL***EL***SL1***SL1a***SL1b***SL2***SL3***SL4***SL5***SL6***SL7***Find***


*** Join SPHCC *** Pass Along Our Website **Fields & Associates Inc. • 150 St. Marks Drive, Suite 202, Stockbridge GA, 30281 • 770-389-3800 ** Suggestion Box *** Free Tour of SPHCC ***